The published fan1.P signal spans 0 to 24,809.445 W in the reference run. It starts at 0 and finishes at 24,809.445. The signed change between those endpoint samples is +24,809.445 W.
What the reference test measures
The Buildings model named StaticReset comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 3,600 seconds. Industry Applied extracted 101 checkpoints for fan1.P and kept the original signed values. The regular output spacing is 36 seconds. The solver may take different internal steps.
The model definition identifies fan1 (Speed Controlled y), fan2 (Speed Controlled y), fan3 (Speed Controlled y). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.
Settings to preserve when repeating the experiment
The published test declares sou.T = 293.15, sin.T = 293.15. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.
Reading the two channels
At 2,664 seconds, fan1.P is 12,064.332 and fan2.P is 13,949.098. Subtracting the second channel from the first gives -1,884.766 W, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.

Reproducing the largest recorded change
Between the stored points at 432 and 468 seconds, fan1.P changes from 2,923.345 to 4,295.825. Subtracting the earlier reading gives +1,372.48 W. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.
The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.
Worked data
Simulation time (s) | fan1.P (W) | fan2.P (W) |
|---|---|---|
0 | 0 | 0 |
432 | 2923.345 | 2923.345 |
468 | 4295.825 | 4295.825 |
900 | 5144.474 | 6608.684 |
1800 | 6831.582 | 8387.678 |
2700 | 12424.07 | 14307.24 |
3600 | 24809.45 | 26445.44 |
Applying the result to an operating site
A lower static setpoint can reduce input while still failing the most demanding branch. Compare fan power with delivered flow and terminal authority. A lower kW trace is meaningful only if the required ventilation duty is maintained.
For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.
Model and data sources
Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.
Cover photograph by Mikhail Nilov, via Pexels. The photograph illustrates the subject. Industry Applied produced the figure and calculations from the linked source.