The published expVes1.m signal spans 19.311 to 26.632 kg in the reference run. It starts at 19.964 and finishes at 21.12. The signed change between those endpoint samples is +1.156 kg.
What the reference test measures
The Buildings model named ExpansionVesselMassConservation comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 7,200 seconds. Industry Applied extracted 101 checkpoints for expVes1.m and kept the original signed values. The regular output spacing is 72 seconds. The solver may take different internal steps.
The model definition identifies expVes1 (Expansion Vessel), expVes2 (Expansion Vessel), pum (Flow Controlled m flow). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.
Settings to preserve when repeating the experiment
The published test declares pum.dp_nominal = 60000, res1.dp_nominal = 20000, res2.dp_nominal = 20000. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.
Reading the two channels
At 4,464 seconds, expVes1.m is 24.522 and expVes2.m is 37.873. Subtracting the second channel from the first gives -13.351 kg, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.

Reproducing the largest recorded change
Between the stored points at 1,800 and 1,872 seconds, expVes1.m changes from 26.632 to 24.065. Subtracting the earlier reading gives -2.567 kg. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.
The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.
Worked data
Simulation time (s) | expVes1.m (kg) | expVes2.m (kg) |
|---|---|---|
0 | 19.96386 | 29.9458 |
1800 | 26.63221 | 37.98574 |
1872 | 24.06495 | 37.34315 |
2664 | 19.31093 | 31.69904 |
3600 | 21.12553 | 28.89028 |
5400 | 26.62438 | 37.99728 |
7200 | 21.1202 | 28.89635 |
Applying the result to an operating site
Track inventories as well as pressure. Fluid mass can move between connected volumes as temperatures change. The more useful conservation test sums the declared control volumes before attributing a change in one vessel to leakage.
For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.
Model and data sources
Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.