The recorded modularAHU.QCoo_flow channel spans -22,317 to 0 W in this reference run. It starts at 0 and ends at 0. The first recorded maximum occurs at 0 seconds and the first minimum at 17,660,160 seconds.

The system being tested

The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named ExampleAHU. The source file places it under Airflow, Air Handling Unit, Modular Air Handling Unit. We used the 101 stored values for modularAHU.QCoo_flow over the interval 0 to 31,536,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name weaDat (Reader TMY3), weaBus1 (Bus). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel modularAHU.QHea_flow covers 0 to 6,360 W. At 17,660,160 s, the primary value is -22,317 and the companion is 6,360. Their signed difference is -28,678 W, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Existing air handler. The simulated modularAHU.QCoo_flow channel runs from -22,317 to 0 W over 31,536,000 seconds.
Existing air handler. The simulated modularAHU.QCoo_flow channel runs from -22,317 to 0 W over 31,536,000 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed modularAHU.QCoo_flow samples by the trapezoidal rule gives -19,012 kWh over 31,536,000 seconds. For each pair, average the two powers in watts and multiply by the interval in seconds. Sum the watt-seconds and divide by 3,600,000. This value refers to the selected simulation connector and should be assigned to a physical load only after confirming the boundary and sign.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

modularAHU.QCoo_flow (W)

modularAHU.QHea_flow (W)

0

0

834.6299

6307200

0

0.000280533

1.26144e+07

0

0.001743498

1.766016e+07

-22317.15

6360.367

1.797552e+07

0

0.005708739

1.89216e+07

-6189.364

2118.013

2.52288e+07

0

5.569922

3.1536e+07

0

793.8143

What to check on site

Identify the connected zones, pressure references and flow direction. Changing a door, leakage path or boundary condition can redistribute the same total flow between branches. A differential pressure alone cannot establish the air quantity reaching a zone.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.