The evaporator temperatures under reverse flow starts at 22 °C and finishes at 20 °C in this reference run. The model stores absolute temperature in kelvin. Its observed minimum and maximum convert to 20 °C and 22 °C.

What the reference test measures

The Buildings model named Carnot_TEva_reverseFlow comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 3,600 seconds. Industry Applied extracted 101 checkpoints for senTEvaEnt.T and kept the original signed values. The regular output spacing is 36 seconds. The solver may take different internal steps.

The model definition identifies senTEvaEnt (Temperature Two Port), senTEvaLvg (Temperature Two Port), chi (Carnot T Eva). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.

Settings to preserve when repeating the experiment

The published test declares mEva_flow.duration = 60, mEva_flow.startTime = 1800, senTConEnt.tau = 0. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.

Reading the two channels

At 0 seconds, senTEvaEnt.T is 295.15 and senTEvaLvg.T is 283.15. Subtracting the second channel from the first gives +12 K, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.

Evaporator temperatures under reverse flow. In the simulated Carnot_TEva_reverseFlow case, senTEvaEnt.T ranges from 293.15 to 295.15 K over 3,600 seconds.
Evaporator temperatures under reverse flow. In the simulated Carnot_TEva_reverseFlow case, senTEvaEnt.T ranges from 293.15 to 295.15 K over 3,600 seconds. Figure by Industry Applied.

Reproducing the largest recorded change

Between the stored points at 1,800 and 1,836 seconds, senTEvaEnt.T changes from 295.15 to 293.15. Subtracting the earlier reading gives -2 K. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.

The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.

Worked data

Simulation time (s)

senTEvaEnt.T (K)

senTEvaLvg.T (K)

0

295.15

283.15

900

295.15

283.15

1800

295.15

283.15

1836

293.15

293.15

2700

293.15

293.15

3600

293.15

293.15

Applying the result to an operating site

A port label identifies a fixed connector even when the fluid changes direction. Record the sign of flow and distinguish an upstream temperature from one named for normal operation. A reversed temperature difference can otherwise be mistaken for a failed sensor.

For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.

Model and data sources

Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.