The senTChiWatRet.T trace covers 7.14 to 20 °C, a temperature span of 12.86 K. The first recorded maximum occurs at 0 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named HeatRecoveryHeatPumpWSE. The source file places it under DHC, ETS, Combined. We used the 101 stored values for senTChiWatRet.T over the interval 0 to 360,000 seconds. This is a simulated test with specified inputs and boundaries.

The reference file contains 42 recorded variables. Alongside the primary output there are ets.tanHeaWat.TTop, ets.tanHeaWat.TBot, senTHeaWatSup.T, senTHeaWatRet.T, ets.heaPum.con.resTHeaSup.TWatSupPreSet. The source and the export are linked independently below so that each reading can be traced back to its calculated channel.

Compare the recorded channels

The companion channel senTChiWatSup.T covers 276.794 to 293.15 K. At 226,800 s, the primary value is 286.532 and the companion is 281.894. Their signed difference is 4.638 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Ets model with heat recovery chiller and waterside economiser. The simulated senTChiWatRet.T channel runs from 280.29 to 293.15 K over 360,000 seconds.
Ets model with heat recovery chiller and waterside economiser. The simulated senTChiWatRet.T channel runs from 280.29 to 293.15 K over 360,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 43,200 to 46,800 seconds. Subtracting 293.15 from 283.962 gives -9.188 K. Its location brackets the change within one saved interval of 3,600 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

senTChiWatRet.T (K)

senTChiWatSup.T (K)

0

293.15

293.15

43200

293.1495

293.1494

46800

283.9619

281.6235

72000

285.5296

282.2842

144000

287.3733

284.3579

208800

280.2898

276.7941

216000

284.6484

282.3289

288000

285.747

282.5608

360000

285.8114

282.2865

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.