The TVol.T trace covers 12.11 to 20.831 °C, a temperature span of 8.721 K. The first recorded maximum occurs at 133,056 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named ElectricHeater. The source file places it under Applications, Data Centers, Chiller Cooled, Equipment. We used the 101 stored values for TVol.T over the interval 0 to 172,800 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name eleHea (Electric Heater), uHea (Boolean Step). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel THeaOut.T covers 285.26 to 298.206 K. At 112,320 s, the primary value is 292.734 and the companion is 298.206. Their signed difference is -5.472 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Equipment electric heater. The simulated TVol.T channel runs from 285.26 to 293.981 K over 172,800 seconds.
Equipment electric heater. The simulated TVol.T channel runs from 285.26 to 293.981 K over 172,800 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 110,592 to 112,320 seconds. Subtracting 289.381 from 292.734 gives 3.353 K. Its location brackets the change within one saved interval of 1,728 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

TVol.T (K)

THeaOut.T (K)

0

289.15

289.15

8640

285.2597

285.2597

34560

291.9734

291.9731

69120

292.329

292.33

103680

289.1508

289.5741

110592

289.3807

289.3806

112320

292.7338

298.2056

133056

293.9807

293.9807

138240

293.6953

293.6953

172800

289.15

290.519

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.