The signed flow trace gives a net 3.099e-08 kg over 60 s, using the trapezoidal rule between saved samples. The smallest and largest reported rates are -1 kg/s and 1 kg/s. Check the positive flow direction in the model before using the sign to describe delivery or return.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named SpecificEnthalpy. The source file places it under Fluid, Sensors. We used the 101 stored values for senStr.port_a.m_flow over the interval 0 to 60 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name sou (Mass Flow Source h), sin (Boundary ph), senFloSou (Specific Enthalpy), senStr (Specific Enthalpy Two Port). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

At 49.8 s, senStr.port_a.m_flow reads -0.66 kg/s and senStr.h_out reads 1,746.2 J/kg. Across the run, the second channel ranges from 45.044 J/kg to 45,300.9 J/kg. Compare the timing of changes on the two traces. A numerical difference between these channels has no demonstrated physical meaning without matching quantity definitions and units.

Enthalpy flow rate sensors. The simulated senStr.port_a.m_flow channel runs from -1 to 1 kg/s over 60 seconds.
Enthalpy flow rate sensors. The simulated senStr.port_a.m_flow channel runs from -1 to 1 kg/s over 60 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed rate over 60 seconds gives a net 3.1e-08 kg. This estimate averages neighbouring stored rates and multiplies by their time separation. Reverse flow reduces the net total. If a process requires gross throughput, calculate forward and reverse transfers separately at the appropriate boundary.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

senStr.port_a.m_flow (kg/s)

senStr.h_out (J/kg)

0

1

45300.95

12

0.6

45300.95

24

0.2

45300.95

36

-0.2

33565.07

48

-0.6

3063.195

49.2

-0.64

2117.844

49.8

-0.6600001

1746.18

60

-1

45.04448

What to check on site

Record the physical quantity and its reference state before checking agreement. A sensor model can include a delay or mixing volume that an algebraic reference omits. Align both acquisition time and location before interpreting a difference as calibration error.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Units in the source model

The component declarations identify the scale of the exported variables. In this run, senStr.h_out uses J/kg. Keep the exact channel name and unit together when exporting data to a historian. Read the component definition.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.