The published senH_flow.H_flow signal spans -65,591.742 to 45,300.945 W in the reference run. It starts at 45,300.945 and finishes at -65,591.742. The signed change between those endpoint samples is -110,892.688 W.
What the reference test measures
The Buildings model named EnthalpyFlowRate comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 60 seconds. Industry Applied extracted 101 checkpoints for senH_flow.H_flow and kept the original signed values. The regular output spacing is 0.6 seconds. The solver may take different internal steps.
The model definition identifies senH_flow (Enthalpy Flow Rate), senMasFlo (Mass Flow Rate), sou (Mass Flow Source T). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.
Settings to preserve when repeating the experiment
The published test declares senH_flow.m_flow_nominal = 2, sou.T = 293.15, sin.T = 313.15. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.
Reading the two channels
The companion channel senMasFlo.m_flow spans -1 to 1 kg/s across its 101 stored values. The primary trace first reaches its recorded maximum at 0 seconds and its minimum at 60 seconds. A time-aligned comparison preserves the meaning and units of each channel.

Reproducing the largest recorded change
Between the stored points at 43.2 and 43.8 seconds, senH_flow.H_flow changes from -28,860.366 to -30,172.205. Subtracting the earlier reading gives -1,311.839 W. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.
The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.
Worked data
Simulation time (s) | senH_flow.H_flow (W) | senMasFlo.m_flow (kg/s) |
|---|---|---|
0 | 45300.95 | 1 |
15 | 22650.47 | 0.5 |
30 | -1.354272e-10 | 0 |
43.2 | -28860.37 | -0.44 |
43.8 | -30172.2 | -0.46 |
45 | -32795.87 | -0.5 |
60 | -65591.74 | -1 |
Applying the result to an operating site
Enthalpy flow combines signed mass flow with the fluid’s specific enthalpy. The reference basis matters for individual streams. When comparing heat transferred across a plant item, use compatible inlet and outlet enthalpies and the actual direction of flow.
For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.
Model and data sources
Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.
Cover photograph by Jakub Zerdzicki, via Pexels. The photograph illustrates the subject. Industry Applied produced the figure and calculations from the linked source.