The published senDyn.V_flow signal spans -8.333 to 8.333 m³/s in the reference run. It starts at 8.333 and finishes at -8.333. The signed change between those endpoint samples is -16.667 m³/s.

What the reference test measures

The Buildings model named VolumeFlowRate comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 60 seconds. Industry Applied extracted 101 checkpoints for senDyn.V_flow and kept the original signed values. The regular output spacing is 0.6 seconds. The solver may take different internal steps.

The model definition identifies senDyn (Volume Flow Rate), senSteSta (Volume Flow Rate), sin (Boundary p T). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.

Settings to preserve when repeating the experiment

The published test declares sin.T = 293.15, senDyn.m_flow_nominal = 10, senDyn.tau = 1. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.

Reading the two channels

At 0 seconds, senDyn.V_flow is 8.333 and senSteSta.V_flow is 8.333. Subtracting the second channel from the first gives 0 m³/s, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.

Dynamic volumetric flow. In the simulated VolumeFlowRate case, senDyn.V_flow ranges from -8.333 to 8.333 m³/s over 60 seconds.
Dynamic volumetric flow. In the simulated VolumeFlowRate case, senDyn.V_flow ranges from -8.333 to 8.333 m³/s over 60 seconds. Figure by Industry Applied.

Reproducing the largest recorded change

Between the stored points at 52.2 and 52.8 seconds, senDyn.V_flow changes from -6.167 to -6.333. Subtracting the earlier reading gives -0.167 m³/s. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.

The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.

Worked data

Simulation time (s)

senDyn.V_flow (m³/s)

senSteSta.V_flow (m³/s)

0

8.333333

8.333333

15

4.166667

4.166667

30

0

0

45

-4.166667

-4.166667

52.2

-6.166666

-6.166666

52.8

-6.333334

-6.333334

60

-8.333333

-8.333333

Applying the result to an operating site

Flow totalisation amplifies persistent offsets, while brief signal lag can partly cancel over a complete cycle. Inspect both the instantaneous traces and the integral over the same period. Record whether the source reports actual or reference-condition volume.

For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.