The dynamic dry-bulb temperature starts at 20 °C and finishes at 39.989 °C in this reference run. The model stores absolute temperature in kelvin. Its observed minimum and maximum convert to 20 °C and 39.989 °C.

What the reference test measures

The Buildings model named TemperatureDryBulb comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 60 seconds. Industry Applied extracted 101 checkpoints for temDyn.T and kept the original signed values. The regular output spacing is 0.6 seconds. The solver may take different internal steps.

The model definition identifies temSteSta (Temperature Two Port), temDyn (Temperature Two Port), amb (Boundary p T). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.

Settings to preserve when repeating the experiment

The published test declares amb.T = 298.15, TDryBul.height = 10, TDryBul.duration = 1. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.

Reading the two channels

At 15.6 seconds, temDyn.T is 298.334 and temSteSta.T is 313.15. Subtracting the second channel from the first gives -14.816 K, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.

Dynamic dry-bulb temperature. In the simulated TemperatureDryBulb case, temDyn.T ranges from 293.15 to 313.139 K over 60 seconds.
Dynamic dry-bulb temperature. In the simulated TemperatureDryBulb case, temDyn.T ranges from 293.15 to 313.139 K over 60 seconds. Figure by Industry Applied.

Reproducing the largest recorded change

Between the stored points at 15 and 15.6 seconds, temDyn.T changes from 293.15 to 298.334. Subtracting the earlier reading gives +5.184 K. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.

The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.

Worked data

Simulation time (s)

temDyn.T (K)

temSteSta.T (K)

0

293.15

298.15

15

293.15

303.15

15.6

298.3342

313.15

30

312.6796

303.15

45

293.1608

293.15

60

313.1389

313.15

Applying the result to an operating site

A moving air temperature can change before a sensor element equilibrates. Compare like-for-like measurement locations, air velocity and mounting. The sensor’s response model and the process transport delay can both contribute to a lag in the trend.

For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.

Model and data sources

Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.