The con.T2Ret.T trace covers 20 to 36.044 °C, a temperature span of 16.044 K. The first recorded maximum occurs at 57,888 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named DualMixing. The source file places it under Fluid, Hydronic Configurations, Passive Networks. We used the 101 stored values for con.T2Ret.T over the interval 0 to 86,400 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name con (Dual Mixing), loa (Load Three Way Valve Control), T2Set (Constant), T1Set (Constant). The source declares TAirEnt_nominal = 24 + 273.15, phiAirEnt_nominal = 0.5. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel con.T2Sup.T covers 293.15 to 309.239 K. At 23,328 s, the primary value is 298.279 and the companion is 308.15. Their signed difference is -9.871 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 21,600 to 22,464 seconds. Subtracting 293.15 from 298.181 gives 5.031 K. Its location brackets the change within one saved interval of 864 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | con.T2Ret.T (K) | con.T2Sup.T (K) |
|---|---|---|
0 | 293.15 | 293.15 |
17280 | 293.15 | 293.15 |
21600 | 293.15 | 293.15 |
22464 | 298.1812 | 308.0373 |
34560 | 304.0031 | 308.1576 |
51840 | 307.7003 | 308.4924 |
57888 | 309.1939 | 309.2393 |
69120 | 304.0597 | 308.15 |
86400 | 308.2054 | 308.599 |
What to check on site
Mark the measurement points on a hydraulic schematic and identify whether the controller holds flow or differential pressure. Record pump command and delivered duty together. A site comparison needs the same branch state, including bypasses and closed valves.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.