The recorded pum.m_flow channel spans 1.856 to 2.493 kg/s in this reference run. It starts at 2 and ends at 2.493. The first recorded maximum occurs at 300 seconds and the first minimum at 150 seconds.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named DiversionOpenLoop. The source file places it under Fluid, Hydronic Configurations, Active Networks. We used the 101 stored values for pum.m_flow over the interval 0 to 300 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name con (Diversion), loa (Load), con1 (Diversion), loa1 (Load). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel con.val.m1_flow starts at 0.9999, ends at 1.09e-06 and has a recorded range of 1.09e-06 to 0.9999 source units. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Reproduce the calculation
Integrating the signed rate over 300 seconds gives a net 629.378 kg. This estimate averages neighbouring stored rates and multiplies by their time separation. Reverse flow reduces the net total. If a process requires gross throughput, calculate forward and reverse transfers separately at the appropriate boundary.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | pum.m_flow (kg/s) | con.val.m1_flow (source units) |
|---|---|---|
0 | 1.999875 | 0.9999362 |
60 | 1.987626 | 0.1350207 |
111 | 2.151214 | 0.04140481 |
114 | 2.113781 | 0.04699709 |
120 | 2.041508 | 0.06045004 |
150 | 1.855782 | 0.2029921 |
180 | 2.041508 | 0.5902111 |
240 | 2.170391 | 0.2850897 |
300 | 2.492681 | 1.092208e-06 |
What to check on site
Mark the measurement points on a hydraulic schematic and identify whether the controller holds flow or differential pressure. Record pump command and delivered duty together. A site comparison needs the same branch state, including bypasses and closed valves.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.