The recorded dxCoo.Q_flow channel spans -25,728 to 0 W in this reference run. It starts at 0 and ends at -25,728. The first recorded maximum occurs at 0 seconds and the first minimum at 3,600 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named DXCooling. The source file places it under Fluid, direct expansion Systems, Cooling. We used the 101 stored values for dxCoo.Q_flow over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name p (Constant), onOff (Integer Step), m_flow (Ramp), TEvaIn (Ramp). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel TEvaIn.y starts at 302.15, ends at 297.15 and has a recorded range of 297.15 to 302.15 source units. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Direct expansion cooling. The simulated dxCoo.Q_flow channel runs from -25,728 to 0 W over 3,600 seconds.
Direct expansion cooling. The simulated dxCoo.Q_flow channel runs from -25,728 to 0 W over 3,600 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed dxCoo.Q_flow samples by the trapezoidal rule gives -12.464 kWh over 3,600 seconds. For each pair, average the two powers in watts and multiply by the interval in seconds. Sum the watt-seconds and divide by 3,600,000. This value refers to the selected simulation connector and should be assigned to a physical load only after confirming the boundary and sign.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

dxCoo.Q_flow (W)

TEvaIn.y (source units)

0

0

302.15

720

0

302.15

1260

-1466.6

302.15

1296

-9413.535

302.15

1440

-12301.19

302.15

2160

-19677.02

302.15

2880

-20034.19

298.15

3600

-25728.08

297.15

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.