The TBor1UTubDyn.T trace covers 20 to 25.096 °C, a temperature span of 5.096 K. The first recorded maximum occurs at 6,150 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named BoreholeDynamics. The source file places it under Fluid, Geothermal, Borefields, Boreholes. We used the 101 stored values for TBor1UTubDyn.T over the interval 0 to 15,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name borHolOneUTubDyn (One U Tube), sou (Mass Flow Source T), sin (Boundary p T), borFieUTubDat (Example). The source declares T_start = 273.15 + 22. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel TBor2UTubDyn.T covers 293.15 to 296.219 K. At 1,800 s, the primary value is 297.192 and the companion is 294.988. Their signed difference is 2.204 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Different borehole models and dynamics. The simulated TBor1UTubDyn.T channel runs from 293.15 to 298.246 K over 15,000 seconds.
Different borehole models and dynamics. The simulated TBor1UTubDyn.T channel runs from 293.15 to 298.246 K over 15,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 0 to 150 seconds. Subtracting 293.15 from 294.149 gives 0.9993 K. Its location brackets the change within one saved interval of 150 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

TBor1UTubDyn.T (K)

TBor2UTubDyn.T (K)

0

293.15

293.15

150

294.1493

293.9397

3000

298.0706

296.1023

6000

298.2459

296.2007

6150

298.2459

296.2004

9000

298.2457

296.2003

12000

298.2457

296.2003

15000

298.2457

296.2003

What to check on site

The thermal history of a borefield matters across repeated loads. Distinguish a fluid outlet reading from pipe wall, grout and far-field temperatures. Record the duration and sign of each heat pulse before comparing an installation with a reference case.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.

Cover photograph by Jakub Zerdzicki, via Pexels. The photograph illustrates the subject. Industry Applied produced the figure and calculations from the linked source.