The recorded thermalZone.TAir temperature spans 14.994 °C to 22.789 °C in this simulation. That is a change of 7.7952 K. The first saved maximum occurs at 23,021,280 s. The source trace and download retain absolute temperatures in kelvin.

The system being tested

The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named ComparisonThermalZoneMoistAndDryAir. The source file places it under Thermal Zones, Reduced Order. We used the 101 stored values for thermalZone.TAir over the interval 0 to 31,536,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name thermalZoneMoistAir (Thermal Zone), weaDat (Reader TMY3), prescribedHeatFlow (Prescribed Heat Flow), sine (Sine). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

At 12,929,760 s, thermalZone.TAir is 294.474 K and thermalZoneMoistAir.TAir is 294.489 K. Subtracting the second value from the first gives -0.015116 K. This is their largest recorded absolute separation. A difference between an inlet and an outlet, or between a command and a response, need not be a measurement error.

Difference between thermal zone and thermal zone moist air. The simulated thermalZone.TAir channel runs from 288.144 to 295.939 K over 31,536,000 seconds.
Difference between thermal zone and thermal zone moist air. The simulated thermalZone.TAir channel runs from 288.144 to 295.939 K over 31,536,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 315,360 to 630,720 seconds. Subtracting 292.342 from 288.453 gives -3.889 K. Its location brackets the change within one saved interval of 315,360 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

thermalZone.TAir (K)

thermalZoneMoistAir.TAir (K)

0

293.15

293.15

315360

292.3423

292.3521

630720

288.453

288.4579

2522880

288.1438

288.1508

6307200

292.2299

292.2379

1.26144e+07

292.7852

292.7931

1.89216e+07

294.0323

294.0404

2.302128e+07

295.939

295.9511

2.52288e+07

293.841

293.8496

3.1536e+07

288.9583

288.9657

What to check on site

Keep the occupied schedule, weather boundary and zone definition with the result. A change in a simulated room condition can reflect the boundary assumptions as well as the component under study. Compare occupied periods and maintain the same observation location.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.