The recorded con.val.dp channel spans 0 to 99,762 Pa in this reference run. It starts at 0 and ends at 0. The first recorded maximum occurs at 55,296 seconds and the first minimum at 0 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named DecouplingTemperature. The source file places it under Fluid, Hydronic Configurations, Active Networks. We used the 101 stored values for con.val.dp over the interval 0 to 86,400 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name dT (Subtract), dTSetAct (Real Extractor), ctl (PID With Operating Mode), dT2SupRet (Subtract). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel pum.dpMachine covers 0 to 100,000 Pa. At 23,328 s, the primary value is 95,024 and the companion is 100,000. Their signed difference is -4,976 Pa, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Decoupling circuit with delta-t control. The simulated con.val.dp channel runs from 0 to 99,762 Pa over 86,400 seconds.
Decoupling circuit with delta-t control. The simulated con.val.dp channel runs from 0 to 99,762 Pa over 86,400 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 78,624 to 79,488 seconds. Subtracting 99,685 from 3,989 gives -95,696 Pa. Its location brackets the change within one saved interval of 864 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

con.val.dp (Pa)

pum.dpMachine (Pa)

0

0

0

17280

0

0

34560

98553.73

100000

51840

99752.55

100000

55296

99761.86

100000

69120

97575.41

100000

78624

99685.08

100000

79488

3988.825

4000

86400

0

0

What to check on site

Mark the measurement points on a hydraulic schematic and identify whether the controller holds flow or differential pressure. Record pump command and delivered duty together. A site comparison needs the same branch state, including bypasses and closed valves.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.