The published bat.SOC signal spans 0.01 to 0.99 fraction of one in the reference run. It starts at 0.1 and finishes at 0.235. The signed change between those endpoint samples is +0.135 fraction of one.

What the reference test measures

The Buildings model named Battery comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 432,000 seconds. Industry Applied extracted 101 checkpoints for bat.SOC and kept the original signed values. The regular output spacing is 4,320 seconds. The solver may take different internal steps.

The model definition identifies bat (Battery), sou (Constant Voltage), loa (Conductor). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.

Settings to preserve when repeating the experiment

The published test declares sou.V = 12, loa.P_nominal = 0, const1.k = -10e3. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.

Reading the two channels

The companion channel bat.P spans -10,000 to 10,000 W across its 101 stored values. The primary trace first reaches its recorded maximum at 99,360 seconds and its minimum at 151,200 seconds. A time-aligned comparison preserves the meaning and units of each channel.

DC battery state of charge. In the simulated Battery case, bat.SOC ranges from 0.01 to 0.99 fraction of one over 432,000 seconds.
DC battery state of charge. In the simulated Battery case, bat.SOC ranges from 0.01 to 0.99 fraction of one over 432,000 seconds. Figure by Industry Applied.

Reproducing the largest recorded change

Between the stored points at 138,240 and 142,560 seconds, bat.SOC changes from 0.879 to 0.546. Subtracting the earlier reading gives -0.333 fraction of one. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.

The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.

Worked data

Simulation time (s)

bat.SOC (fraction)

bat.P (W)

0

0.1

0

99360

0.99

0

108000

0.99

0

138240

0.8788889

-10000

142560

0.5455555

-10000

151200

0.01

0

216000

0.99

0

324000

0.01

0

432000

0.235

10000

Applying the result to an operating site

State of charge represents stored energy, while terminal power has a sign and an instantaneous value. Integrate signed power across comparable boundaries and account for efficiency when reconciling a state change with meter data.

For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.

Model and data sources

Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.