The recorded TCWLeaTow.T temperature spans 13.563 °C to 22.341 °C in this simulation. That is a change of 8.7775 K. The first saved maximum occurs at 13,185,504 s. The source trace and download retain absolute temperatures in kelvin.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named ContinuousTimeControl. The source file places it under Chiller Plant, Data Center. We used the 101 stored values for TCWLeaTow.T over the interval 13,046,400 to 13,651,200 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name triAndRes (Trim And Respond Continuous Time Approximation). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

At 13,064,544 s, TCWLeaTow.T is 286.713 K and TCHWEntChi.T is 290.826 K. Subtracting the second value from the first gives -4.1132 K. This is their largest recorded absolute separation. A difference between an inlet and an outlet, or between a command and a response, need not be a measurement error.

Data centre that approximates the trim and respond logic. The simulated TCWLeaTow.T channel runs from 286.713 to 295.491 K over 604,800 seconds.
Data centre that approximates the trim and respond logic. The simulated TCWLeaTow.T channel runs from 286.713 to 295.491 K over 604,800 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 13,046,400 to 13,052,448 seconds. Subtracting 293.15 from 287.259 gives -5.891 K. Its location brackets the change within one saved interval of 6,048 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

TCWLeaTow.T (K)

TCHWEntChi.T (K)

1.30464e+07

293.15

293.15

1.305245e+07

287.2595

291.2634

1.306454e+07

286.7132

290.8264

1.316736e+07

292.8333

295.7224

1.31855e+07

295.4907

297.8484

1.328832e+07

289.4654

293.0282

1.340928e+07

287.9405

291.8082

1.353024e+07

292.2501

295.256

1.36512e+07

287.3513

291.3369

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.