The data-centre supply and room temperatures starts at 20 °C and finishes at 17.966 °C in this reference run. The model stores absolute temperature in kelvin. Its observed minimum and maximum convert to 17.901 °C and 20 °C.

What the reference test measures

The Buildings model named DXCooledAirsideEconomizer comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 1.188e+07 to 1.26e+07 seconds. Industry Applied extracted 101 checkpoints for senTemSupAir.T and kept the original signed values. The regular output spacing is 7,200 seconds. The solver may take different internal steps.

The model definition identifies roo (Simplified Room), senTemSupAir (Temperature Two Port), varSpeDX (Variable Speed). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.

Settings to preserve when repeating the experiment

The published test declares varSpeDX.dp_nominal = 400, dam2.y_start = 0. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.

Reading the two channels

At 1.217e+07 seconds, senTemSupAir.T is 291.051 and roo.TRooAir is 298.14. Subtracting the second channel from the first gives -7.089 K, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.

Data-centre supply and room temperatures. In the simulated DXCooledAirsideEconomizer case, senTemSupAir.T ranges from 291.051 to 293.15 K over 720,000 seconds.
Data-centre supply and room temperatures. In the simulated DXCooledAirsideEconomizer case, senTemSupAir.T ranges from 291.051 to 293.15 K over 720,000 seconds. Figure by Industry Applied.

Reproducing the largest recorded change

Between the stored points at 1.188e+07 and 1.189e+07 seconds, senTemSupAir.T changes from 293.15 to 291.13. Subtracting the earlier reading gives -2.02 K. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.

The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.

Worked data

Simulation time (s)

senTemSupAir.T (K)

roo.TRooAir (K)

1.188e+07

293.15

293.15

1.18872e+07

291.13

298.15

1.206e+07

291.1314

298.1499

1.2168e+07

291.051

298.1404

1.224e+07

291.1299

298.15

1.242e+07

291.1202

298.1501

1.26e+07

291.1164

298.1491

Applying the result to an operating site

Supply-air temperature and room-air temperature represent different parts of the cooling system. Compare outdoor conditions, airside mode and direct-expansion cooling power as well. A short supply-air excursion does not immediately establish a change in rack inlet conditions.

For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.

Model and data sources

Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.