The recorded mod.m_flow channel spans 8.89e-08 to 1 kg/s in this reference run. It starts at 8.89e-08 and ends at 1. The first recorded maximum occurs at 122 seconds and the first minimum at 0 seconds.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named Dampers. The source file places it under Templates, Components. We used the 101 stored values for mod.m_flow over the interval 0 to 200 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name bouAirEnt (Boundary p T), bouAirLvg (Boundary p T), mod (Damper), bus (Bus). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel pre.m_flow covers 0.0101 to 0.9876 kg/s. At 68 s, the primary value is 0.1799 and the companion is 0.5733. Their signed difference is -0.3934 kg/s, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Reproduce the calculation
Integrating the signed rate over 200 seconds gives a net 109.821 kg. This estimate averages neighbouring stored rates and multiplies by their time separation. Reverse flow reduces the net total. If a process requires gross throughput, calculate forward and reverse transfers separately at the appropriate boundary.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | mod.m_flow (kg/s) | pre.m_flow (kg/s) |
|---|---|---|
0 | 8.888889e-08 | 0.01009989 |
40 | 0.03247645 | 0.3422452 |
80 | 0.2932554 | 0.6714978 |
118 | 0.9521427 | 0.9734386 |
120 | 0.9988877 | 0.9873147 |
122 | 1 | 0.9876276 |
160 | 1 | 0.9876275 |
200 | 1 | 0.9876275 |
What to check on site
Distinguish the component characteristic from the installed system response. Record the pressure or temperature on both sides as applicable, the direction of flow and the actuator command. Compare a change at constant demand with one caused by a different load.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.

