The recorded EHeaAct.y channel spans 0 to 34,642,968,576 source units in this reference run. It starts at 0 and ends at 34,642,968,576. The first recorded maximum occurs at 604,800 seconds and the first minimum at 0 seconds.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named CouplingTimeSeries. The source file places it under DHC, Loads. We used the 101 stored values for EHeaAct.y over the interval 0 to 604,800 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name bui (Building Time Series), sinHeaWat (Boundary p T), sinChiWat (Boundary p T), THeaWatSup (Real Expression). The source declares perAve = 600. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel EHeaReq.y covers 0 to 34,647,805,952 source units. At 562,464 s, the primary value is 31,231,528,960 and the companion is 31,243,905,024. Their signed difference is -12,376,064 source units, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 538,272 to 544,320 seconds. Subtracting 29,057,533,952 from 29,810,733,056 gives 753,199,104 source units. Its location brackets the change within one saved interval of 6,048 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | EHeaAct.y (source units) | EHeaReq.y (source units) |
|---|---|---|
0 | 0 | 0 |
120960 | 4.688443e+09 | 4.691253e+09 |
241920 | 9.526467e+09 | 9.530324e+09 |
362880 | 1.570235e+10 | 1.570681e+10 |
483840 | 2.483471e+10 | 2.483918e+10 |
538272 | 2.905753e+10 | 2.906657e+10 |
544320 | 2.981073e+10 | 2.982212e+10 |
604800 | 3.464297e+10 | 3.464781e+10 |
What to check on site
Keep the occupied schedule, weather boundary and zone definition with the result. A change in a simulated room condition can reflect the boundary assumptions as well as the component under study. Compare occupied periods and maintain the same observation location.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.