The wseOpe.uFanSpe trace ranges from 0 to 1 across 101 saved checkpoints. It begins at 0 and finishes at 1 after 3,600 s of test time. The source identifies the channel scale as dimensionless. Its first saved maximum occurs at 216 s.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named WSEOperation. The source file places it under Controls, OBC, ASHRAE, G36, Plants, Chillers, Towers, Fan Speed, Enabled WSE, Subsequences. We used the 101 stored values for wseOpe.uFanSpe over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name wseOpe (WSE Operation), chiSup (Sin), chiSupSet (Constant), ram1 (Ramp). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

At 2,052 s, wseOpe.uFanSpe reads 0.94403 and wseOpe.TChiWatSup reads 281.095 K. Across the run, the second channel ranges from 279.751 K to 282 K. Compare the timing of changes on the two traces. A numerical difference between these channels has no demonstrated physical meaning without matching quantity definitions and units.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 2,016 to 2,052 seconds. Subtracting 0.3508 from 0.944 gives 0.5932 source units. Its location brackets the change within one saved interval of 36 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

wseOpe.uFanSpe (dimensionless)

wseOpe.TChiWatSup (K)

0

0

280.25

216

1

280.5923

720

1

280.5439

1440

0.1

279.7745

2016

0.3508269

281.0223

2052

0.9440269

281.0952

2160

1

281.2755

2880

1

281.1061

3600

1

282

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Units in the source model

The component declarations identify the scale of the exported variables. In this run, wseOpe.uFanSpe uses dimensionless and wseOpe.TChiWatSup uses K. Keep the exact channel name and unit together when exporting data to a historian. Read the component definition.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.