The rehBoxCon.TDis trace covers 15 to 17 °C, a temperature span of 2 K. The first recorded maximum occurs at 72,576 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named Controller. The source file places it under Controls, OBC, ASHRAE, G36, Terminal Units, Reheat. We used the 101 stored values for rehBoxCon.TDis over the interval 0 to 86,400 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name rehBoxCon (Controller), TZon (Sin), disAirTem (Ramp), winSta (Pulse). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel rehBoxCon.TSup covers 285.15 to 287.15 K. At 79,488 s, the primary value is 290.15 and the companion is 285.152. Their signed difference is 4.998 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 31,104 to 31,968 seconds. Subtracting 288.257 from 288.297 gives 0.04001 K. Its location brackets the change within one saved interval of 864 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | rehBoxCon.TDis (K) | rehBoxCon.TSup (K) |
|---|---|---|
0 | 288.15 | 286.15 |
17280 | 288.15 | 285.5622 |
31104 | 288.2567 | 286.6317 |
31968 | 288.2967 | 286.7874 |
34560 | 288.4167 | 287.101 |
51840 | 289.2167 | 285.1989 |
69120 | 290.0167 | 286.7378 |
72576 | 290.15 | 286.0247 |
86400 | 290.15 | 286.15 |
What to check on site
Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.