The recorded fan.P channel spans 0 to 400.57 W in this reference run. It starts at 0 and ends at 400.57. The first recorded maximum occurs at 1,968 seconds and the first minimum at 0 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named ControlledFan. The source file places it under Fluid, Data Centers, Racks. We used the 101 stored values for fan.P over the interval 0 to 2,400 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name con (Outlet Temperature), fan (Fan), res (Pressure Drop), vol (Mixing Volume). The source declares PFan_nominal = 400, T_start = 293.15, V_flow_nominal = 0.2 * 2. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel fan.y starts at 0, ends at 1 and has a recorded range of 0 to 1 source units. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Controlled fan. The simulated fan.P channel runs from 0 to 400.57 W over 2,400 seconds.
Controlled fan. The simulated fan.P channel runs from 0 to 400.57 W over 2,400 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed fan.P samples by the trapezoidal rule gives 0.09117 kWh over 2,400 seconds. For each pair, average the two powers in watts and multiply by the interval in seconds. Sum the watt-seconds and divide by 3,600,000. This value refers to the selected simulation connector and should be assigned to a physical load only after confirming the boundary and sign.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

fan.P (W)

fan.y (source units)

0

0

0

480

0.9728416

0.1330047

960

20.22978

0.3696332

1440

112.0443

0.6539897

1920

367.0836

0.9713212

1944

387.078

0.9886457

1968

400.57

1

2400

400.57

1

What to check on site

Identify which part of the system the selected output represents, and retain the surrounding boundary conditions. Compare the same event and operating duty in both records. Record the equipment configuration if a later change could alter the test result.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.