The ctlPumPriDedComDp.dpChiWatLoc trace ranges from 4,715.3 Pa to 12,000 Pa across 101 saved checkpoints. It begins at 10,000 Pa and finishes at 5,333.3 Pa after 5,000 s of test time. The source identifies the channel scale as Pa. Its first saved maximum occurs at 1,500 s.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named VariableSpeedWithHeatPumps. The source file places it under Templates, Plants, Controls, Pumps, Primary. We used the 101 stored values for ctlPumPriDedComDp.dpChiWatLoc over the interval 0 to 5,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name ctlPumPriHdrHea (Variable Speed With Heat Pumps), ctlPumPriHdr (Variable Speed With Heat Pumps), ctlPumPriDedCom (Variable Speed With Heat Pumps), ctlPumPriDedSep (Variable Speed With Heat Pumps). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

At 4,500 s, ctlPumPriDedComDp.dpChiWatLoc is 5,000 Pa and ctlPumPriHdrHeaDp.dpHeaWatLoc is 27,878.7 Pa. Subtracting the second value from the first gives -22,878.7 Pa. This is their largest recorded absolute separation. A difference between an inlet and an outlet, or between a command and a response, need not be a measurement error.

Control logic of variable-speed primary pumps in heat pump plants. The simulated ctlPumPriDedComDp.dpChiWatLoc channel runs from 4,715 to 12,000 source units over 5,000 seconds.
Control logic of variable-speed primary pumps in heat pump plants. The simulated ctlPumPriDedComDp.dpChiWatLoc channel runs from 4,715 to 12,000 source units over 5,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 4,000 to 4,050 seconds. Subtracting 8,667 from 8,187 gives -479.536 source units. Its location brackets the change within one saved interval of 50 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

ctlPumPriDedComDp.dpChiWatLoc (Pa)

ctlPumPriHdrHeaDp.dpHeaWatLoc (Pa)

0

10000

3000

1000

10000

7500

1500

12000

12128.68

2000

10000

18000

3000

10000

28500

4000

8666.667

30000

4050

8187.131

29764.62

4700

4715.299

27326.98

5000

5333.333

27000

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Units in the source model

The component declarations identify the scale of the exported variables. In this run, ctlPumPriDedComDp.dpChiWatLoc uses Pa and ctlPumPriHdrHeaDp.dpHeaWatLoc uses Pa. Keep the exact channel name and unit together when exporting data to a historian. Read the component definition.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.