The recorded valAut25.dp channel spans 25,000 to 100,000 Pa in this reference run. It starts at 100,000 and ends at 25,000. The first recorded maximum occurs at 0 seconds and the first minimum at 100 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named TwoWayOpenLoop. The source file places it under Fluid, Hydronic Configurations. We used the 101 stored values for valAut25.dp over the interval 0 to 100 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name sup (Boundary p T), ret (Boundary p T), ter50 (Pressure Drop), valAut50 (Two Way Equal Percentage). The source declares mLiq_flow_nominal = 1, p_min = 2E5, dp_nominal = 1E5. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel valAut75.dp covers 75,000 to 100,000 Pa. At 100 s, the primary value is 25,000 and the companion is 75,000. Their signed difference is -50,000 Pa, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Concept of the authority for two-way valves and open-loop control. The simulated valAut25.dp channel runs from 25,000 to 100,000 Pa over 100 seconds.
Concept of the authority for two-way valves and open-loop control. The simulated valAut25.dp channel runs from 25,000 to 100,000 Pa over 100 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 85 to 86 seconds. Subtracting 51,874 from 49,919 gives -1,955 Pa. Its location brackets the change within one saved interval of 1 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

valAut25.dp (Pa)

valAut75.dp (Pa)

0

99999.95

99999.99

20

99143.02

99850.08

40

97233.54

99608.23

60

88401.43

98556.3

80

61448.32

93483.34

85

51873.99

90654.99

86

49918.86

89970.75

100

25000

75000

What to check on site

Mark the measurement points on a hydraulic schematic and identify whether the controller holds flow or differential pressure. Record pump command and delivered duty together. A site comparison needs the same branch state, including bypasses and closed valves.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.