The senTem.T trace covers 17.068 to 29.725 °C, a temperature span of 12.658 K. The first recorded maximum occurs at 13,104 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.
The system being tested
The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named SensibleCooler. The source file places it under Airflow, Air Handling Unit, Modular Air Handling Unit, Components. We used the 101 stored values for senTem.T over the interval 0 to 14,400 seconds. This is a simulated test with specified inputs and boundaries.
The reference file contains 8 recorded variables. Alongside the primary output there are senTem.T, senCooRea.TAirOut, resT.y, senCooRea1.Q_flow, cooFlu1.Q_flow. The source and the export are linked independently below so that each reading can be traced back to its calculated channel.
Compare the recorded channels
The companion channel senCooRea.TAirOut starts at 290.218, ends at 302.875 and has a recorded range of 290.218 to 302.875 source units. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 0 to 144 seconds. Subtracting 293.15 from 290.342 gives -2.808 K. Its location brackets the change within one saved interval of 144 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | senTem.T (K) | senCooRea.TAirOut (source units) |
|---|---|---|
0 | 293.15 | 290.2179 |
144 | 290.3424 | 290.2179 |
720 | 290.2178 | 290.2179 |
2880 | 290.2179 | 290.2179 |
5760 | 300.2175 | 300.2179 |
8640 | 300.2335 | 300.2338 |
11520 | 301.4962 | 301.5565 |
13104 | 302.8753 | 302.8752 |
14400 | 302.8753 | 302.8752 |
What to check on site
Identify the connected zones, pressure references and flow direction. Changing a door, leakage path or boundary condition can redistribute the same total flow between branches. A differential pressure alone cannot establish the air quantity reaching a zone.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.