The chi.TSet trace covers 7.22 to 12.78 °C, a temperature span of 5.56 K. The first recorded maximum occurs at 864 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named ChillerSetPointControl. The source file places it under Chiller Plant, Data Center, Controls. We used the 101 stored values for chi.TSet over the interval 0 to 86,400 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name chi (Electric EIR), coi (Constant Effectiveness), limPID (Lim PID), pum (Flow Controlled m flow). The source declares mAir_flow_nominal = 61.6*2, COPc_nominal = 3, mCHW_flow_nominal = 15.2. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel TRet.T covers 286.651 to 294.591 K. At 25,056 s, the primary value is 280.37 and the companion is 291.559. Their signed difference is -11.189 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 0 to 864 seconds. Subtracting 283.15 from 285.93 gives 2.78 K. Its location brackets the change within one saved interval of 864 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | chi.TSet (K) | TRet.T (K) |
|---|---|---|
0 | 283.15 | 293.15 |
864 | 285.93 | 294.5911 |
4320 | 280.37 | 291.5021 |
17280 | 280.37 | 287.2469 |
34560 | 280.37 | 286.6717 |
51840 | 280.37 | 287.7667 |
69120 | 280.37 | 289.7797 |
86400 | 280.37 | 291.3282 |
What to check on site
Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.