The recorded chiWatSupSet.TChiWatSupSet temperature spans 7 °C to 18 °C in this simulation. That is a change of 11 K. The first saved maximum occurs at 0 s. The source trace and download retain absolute temperatures in kelvin.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named ChilledWaterSupply. The source file places it under Controls, OBC, ASHRAE, G36, Plants, Chillers, Set Points. We used the 101 stored values for chiWatSupSet.TChiWatSupSet over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name chiWatSupSet (Chilled Water Supply), plaRes (Ramp). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The two named channels have separate paths in the model. chiWatSupSet.TChiWatSupSet begins at 291.15 and ends at 280.15. chiWatSupSet.uChiWatPlaRes begins at 0 and ends at 1. The reference export supplies numerical samples but does not attach a physical unit to these fields. Use the linked model declarations to establish the quantity and units of each channel before calculating a difference or assigning it a physical meaning.
Reproduce the calculation
The largest absolute change between consecutive stored points appears from 1,800 to 1,836 seconds. Subtracting 291.15 from 290.93 gives -0.22 source units. Its location brackets the change within one saved interval of 36 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | chiWatSupSet.TChiWatSupSet (K) | chiWatSupSet.uChiWatPlaRes (dimensionless) |
|---|---|---|
0 | 291.15 | 0 |
720 | 291.15 | 0.2 |
1440 | 291.15 | 0.4 |
1800 | 291.15 | 0.5 |
1836 | 290.93 | 0.51 |
2160 | 288.95 | 0.6 |
2880 | 284.55 | 0.8 |
3600 | 280.15 | 1 |
What to check on site
Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Units in the source model
The component declarations identify the scale of the exported variables. In this run, chiWatSupSet.TChiWatSupSet uses K and chiWatSupSet.uChiWatPlaRes uses dimensionless. Keep the exact channel name and unit together when exporting data to a historian. Read the component definition.
Checking the two recorded channels
At 1,836 s, chiWatSupSet.TChiWatSupSet reads 290.93 K and chiWatSupSet.uChiWatPlaRes reads 0.51. Across the run, the second channel ranges from 0 to 1. Compare the timing of changes on the two traces. A numerical difference between these channels has no demonstrated physical meaning without matching quantity definitions and units.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.