The senTCDU_b.T trace covers 33.26 to 42.07 °C, a temperature span of 8.811 K. The first recorded maximum occurs at 4,536 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named CDU_epsNTU. The source file places it under Fluid, Data Centers, CD Us, Liquid To Liquid. We used the 101 stored values for senTCDU_b.T over the interval 0 to 7,200 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name dpSet (Constant). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel senTRac_a.T covers 303.15 to 316.22 K. At 0 s, the primary value is 306.41 and the companion is 303.15. Their signed difference is 3.26 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Cdu with varying load on the it side. The simulated senTCDU_b.T channel runs from 306.41 to 315.22 K over 7,200 seconds.
Cdu with varying load on the it side. The simulated senTCDU_b.T channel runs from 306.41 to 315.22 K over 7,200 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 0 to 72 seconds. Subtracting 306.41 from 314.052 gives 7.643 K. Its location brackets the change within one saved interval of 72 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

senTCDU_b.T (K)

senTRac_a.T (K)

0

306.4098

303.15

72

314.0524

314.5146

1440

314.2052

315.3384

2880

314.1414

314.5918

4320

314.7614

315.1497

4536

315.2205

316.2203

5760

314.2052

315.3384

7200

314.7473

315.1369

What to check on site

Identify which part of the system the selected output represents, and retain the surrounding boundary conditions. Compare the same event and operating duty in both records. Record the equipment configuration if a later change could alter the test result.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.