The roo.surf_surBou[3].T trace covers 0.03109 to 2.305 °C, a temperature span of 2.274 K. The first recorded maximum occurs at 1,836 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named NaturalConvectionWithControl. The source file places it under Thermal Zones, Detailed, FFD. We used the 101 stored values for roo.surf_surBou[3].T over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name TSet (Constant). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel roo.surf_surBou[4].T covers 273.181 to 275.455 K. At 792 s, the primary value is 274.541 and the companion is 274.541. Their signed difference is 3.05e-05 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Case of natural convection with feedback loop control. The simulated roo.surf_surBou[3].T channel runs from 273.181 to 275.455 K over 3,600 seconds.
Case of natural convection with feedback loop control. The simulated roo.surf_surBou[3].T channel runs from 273.181 to 275.455 K over 3,600 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 180 to 216 seconds. Subtracting 273.478 from 273.595 gives 0.1174 K. Its location brackets the change within one saved interval of 36 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

roo.surf_surBou[3].T (K)

roo.surf_surBou[4].T (K)

0

273.1811

273.1811

180

273.4777

273.4777

216

273.5951

273.5951

720

274.41

274.41

1440

275.2657

275.2657

1836

275.4546

275.4546

2160

275.3925

275.3925

2880

275.1465

275.1465

3600

275.2384

275.2384

What to check on site

Keep the occupied schedule, weather boundary and zone definition with the result. A change in a simulated room condition can reflect the boundary assumptions as well as the component under study. Compare occupied periods and maintain the same observation location.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.