The vol.T trace covers 10.432 to 26.955 °C, a temperature span of 16.522 K. The first recorded maximum occurs at 44,064 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named CarnotWithLosses_OneRoomRadiator. The source file places it under Fluid, Heat Pumps, Modular Reversible. We used the 101 stored values for vol.T over the interval 0 to 86,400 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name heaPum (Carnot With Losses), temAmbBas (Constant). The source declares perHeaLos = 0.01. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel temRet.T covers 283.75 to 323.15 K. At 0 s, the primary value is 293.15 and the companion is 323.15. Their signed difference is -30 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Carnot with losses one room radiator. The simulated vol.T channel runs from 283.582 to 300.105 K over 86,400 seconds.
Carnot with losses one room radiator. The simulated vol.T channel runs from 283.582 to 300.105 K over 86,400 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 51,840 to 52,704 seconds. Subtracting 296.767 from 285.65 gives -11.116 K. Its location brackets the change within one saved interval of 864 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

vol.T (K)

temRet.T (K)

0

293.15

323.15

17280

293.562

314.047

34560

291.9901

306.1452

44064

300.1047

304.3914

51840

296.7666

288.5524

52704

285.6503

283.7503

53568

283.5825

288.4706

69120

291.7195

306.9826

86400

293.0017

308.3195

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.