The recorded chi.P channel spans 14,737 to 68,469 W in this reference run. It starts at 68,469 and ends at 14,737. The first recorded maximum occurs at 0 seconds and the first minimum at 1,872 seconds.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named Carnot_TEva. The source file places it under Fluid, Chillers. We used the 101 stored values for chi.P over the interval 0 to 3,600 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name chi (Carnot evaporator temperature), TEvaLvg (Ramp), mCon_flow (Gain), QCon_flow (Add). The source declares dTEva_nominal = -10, dTCon_nominal = 10, COPc_nominal = 3, QEva_flow_nominal = -100E3. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel chi.QEva_flow starts at -159,390, ends at -59,771 and has a recorded range of -159,390 to -59,771 W. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Carnot evaporator temperature. The simulated chi.P channel runs from 14,737 to 68,469 W over 3,600 seconds.
Carnot evaporator temperature. The simulated chi.P channel runs from 14,737 to 68,469 W over 3,600 seconds. Figure by Industry Applied.

Reproduce the calculation

Integrating the signed chi.P samples by the trapezoidal rule gives 42.04 kWh over 3,600 seconds. For each pair, average the two powers in watts and multiply by the interval in seconds. Sum the watt-seconds and divide by 3,600,000. This value refers to the selected simulation connector and should be assigned to a physical load only after confirming the boundary and sign.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

chi.P (W)

chi.QEva_flow (W)

0

68469.09

-159390.5

720

68469.09

-159390.5

1440

68469.09

-159390.5

1800

68469.09

-159390.5

1836

31588.42

-99619.05

1872

14737.1

-59771.43

2160

14737.1

-59771.43

2880

14737.1

-59771.43

3600

14737.1

-59771.43

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.