The published optSta.tOpt signal spans 0 to 7,953.379 seconds in the reference run. It starts at 0 and finishes at 1,060.291. The signed change between those endpoint samples is +1,060.291 seconds.

What the reference test measures

The Buildings model named OptimalStartHeatingCooling comes from Lawrence Berkeley National Laboratory. The saved result covers simulation time 0 to 2.419e+06 seconds. Industry Applied extracted 101 checkpoints for optSta.tOpt and kept the original signed values. The regular output spacing is 24,192 seconds. The solver may take different internal steps.

The model definition identifies optSta (Optimal Start), TRoo (Integrator), TSetCooOcc (Constant). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.

Settings to preserve when repeating the experiment

The published test declares TRoo.k = 0.0000004, TOutBase.amplitude = 5, UA.k = 25. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.

Reading the two channels

At 725,760 seconds, optSta.tOpt is 5,739.301 and optSta.optHea.tOpt is 0. Subtracting the second channel from the first gives +5,739.301 seconds, the largest absolute separation on their common saved grid. The channels have distinct roles in the model, so this difference describes the two traces and is not a calibrated instrument error.

Calculated optimal start time. In the simulated OptimalStartHeatingCooling case, optSta.tOpt ranges from 0 to 7,953.379 seconds over 2.419e+06 seconds.
Calculated optimal start time. In the simulated OptimalStartHeatingCooling case, optSta.tOpt ranges from 0 to 7,953.379 seconds over 2.419e+06 seconds. Figure by Industry Applied.

Reproducing the largest recorded change

Between the stored points at 0 and 24,192 seconds, optSta.tOpt changes from 0 to 7,953.379. Subtracting the earlier reading gives +7,953.379 seconds. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.

The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.

Worked data

Simulation time (s)

optSta.tOpt (s)

optSta.optHea.tOpt (s)

0

0

0

24192

7953.379

7953.379

604800

2164.974

2164.974

1209600

1060.463

0

1814400

2164.943

2164.943

2419200

1060.291

0

Applying the result to an operating site

Compare calculated lead time with the actual occupancy schedule and zone trajectory. Reaching a target by the occupancy time is a different objective from starting early every day. Field evaluation needs representative weather and load periods.

For an Australian monitoring project, write the intended sample interval, timestamp convention, tag units and missed-update policy into the acceptance record. Re-run this comparison on the installed signal path and retain the raw export so a later dashboard change can be checked against the same baseline.

Model and data sources

Model definition. Original numerical reference series. Simulation and plotting script. Source project. Download the worked checkpoints as CSV.