The senTemInlRet.T trace covers 48 to 52 °C, a temperature span of 4 K. The first recorded maximum occurs at 48,565,440 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named TwoPipesConduit. The source file places it under Fluid, Fixed Resistances, Buried Pipes. We used the 101 stored values for senTemInlRet.T over the interval 0 to 63,072,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name cliCon (Boston), pipSup (Plug Flow Pipe), gro (Ground Coupling), TinSup (Sine). The source declares dCon = 0.3, len = 1000, xConWal = 0.01. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel senTemInlSup.T covers 338.154 to 348.147 K. At 35,951,040 s, the primary value is 323.925 and the companion is 347.779. Their signed difference is -23.854 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Buried conduit housing a supply and return pipe. The simulated senTemInlRet.T channel runs from 321.15 to 325.15 K over 63,072,000 seconds.
Buried conduit housing a supply and return pipe. The simulated senTemInlRet.T channel runs from 321.15 to 325.15 K over 63,072,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 0 to 630,720 seconds. Subtracting 323.15 from 324.875 gives 1.725 K. Its location brackets the change within one saved interval of 630,720 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

senTemInlRet.T (K)

senTemInlSup.T (K)

0

323.15

343.15

630720

324.875

344.4103

1.26144e+07

322.3685

338.5141

2.52288e+07

321.1503

339.6767

3.78432e+07

322.4333

345.1837

4.856544e+07

325.1498

346.6358

5.04576e+07

324.6127

348.1469

6.3072e+07

324.9626

344.8601

What to check on site

Distinguish the component characteristic from the installed system response. Record the pressure or temperature on both sides as applicable, the direction of flow and the actuator command. Compare a change at constant demand with one caused by a different load.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.