The recorded boiBus.Q_flow channel spans 8,887 to 22,988 W in this reference run. It starts at 22,988 and ends at 8,887. The first recorded maximum occurs at 0 seconds and the first minimum at 1,200 seconds.
The system being tested
The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named BoilerGeneric. The source file places it under Fluid, Boiler CHP. We used the 101 stored values for boiBus.Q_flow over the interval 0 to 1,200 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name source (Mass Flow Source T), ramp (Ramp), sink (Boundary p T), sine (Sine). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel boiBus.fuelPower starts at 23,318, ends at 10,160 and has a recorded range of 10,160 to 23,318 source units. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Reproduce the calculation
Integrating the signed boiBus.Q_flow samples by the trapezoidal rule gives 6.481 kWh over 1,200 seconds. For each pair, average the two powers in watts and multiply by the interval in seconds. Sum the watt-seconds and divide by 3,600,000. This value refers to the selected simulation connector and should be assigned to a physical load only after confirming the boundary and sign.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | boiBus.Q_flow (W) | boiBus.fuelPower (source units) |
|---|---|---|
0 | 22987.69 | 23318.34 |
240 | 22260.1 | 23318.34 |
480 | 20870.37 | 23318.34 |
636 | 20385.81 | 23318.34 |
648 | 14507.42 | 16595.23 |
720 | 20381.77 | 23318.34 |
960 | 20358.98 | 23318.34 |
1200 | 8887.481 | 10159.93 |
What to check on site
Compare fuel or electrical input with useful heat at a declared delivery boundary. Include the warm-up interval and any period on standby. Separate a temperature setpoint from the measured outlet and keep auxiliary energy in a stated part of the balance.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.