The recorded thermalZoneTwoElements.TAir temperature spans 20.913 °C to 32.363 °C in this simulation. That is a change of 11.45 K. The first saved maximum occurs at 574,560 s. The source trace and download retain absolute temperatures in kelvin.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named RoomWithLatentGain. The source file places it under Thermal Zones, Reduced Order. We used the 101 stored values for thermalZoneTwoElements.TAir over the interval 0 to 604,800 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name senRelHum (Relative Humidity), senMasFra (Mass Fraction). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

At 459,648 s, thermalZoneTwoElements.TAir reads 303.076 K and senRelHum.phi reads 0.41691. Across the run, the second channel ranges from 0.37428 to 0.65414. Compare the timing of changes on the two traces. A numerical difference between these channels has no demonstrated physical meaning without matching quantity definitions and units.

Based on VDI 6007 case 12, with latent heat gain added. The simulated thermalZoneTwoElements.TAir channel runs from 294.063 to 305.513 K over 604,800 seconds.
Based on VDI 6007 case 12, with latent heat gain added. The simulated thermalZoneTwoElements.TAir channel runs from 294.063 to 305.513 K over 604,800 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 453,600 to 459,648 seconds. Subtracting 299.931 from 303.076 gives 3.145 K. Its location brackets the change within one saved interval of 6,048 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

thermalZoneTwoElements.TAir (K)

senRelHum.phi (dimensionless)

0

295.15

0.6120146

12096

294.0628

0.6541358

120960

299.237

0.5608009

241920

300.3592

0.4496126

362880

298.977

0.4863119

453600

299.9311

0.4596961

459648

303.0761

0.4169056

483840

304.3036

0.4237415

574560

305.5132

0.3957306

604800

301.866

0.410621

What to check on site

Keep the occupied schedule, weather boundary and zone definition with the result. A change in a simulated room condition can reflect the boundary assumptions as well as the component under study. Compare occupied periods and maintain the same observation location.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Units in the source model

The component declarations identify the scale of the exported variables. In this run, senRelHum.phi uses dimensionless. Keep the exact channel name and unit together when exporting data to a historian. Read the component definition.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.