The senTLoaSup.T trace covers 20 to 30 °C, a temperature span of 10 K. The first recorded maximum occurs at 10,368 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named HeatPump. The source file places it under DHC, ETS, Combined, Subsystems. We used the 101 stored values for senTLoaSup.T over the interval 0 to 172,800 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name supAmb (Boundary p T), sinAmb (Boundary p T), souLoa (Boundary p T), sin (Sine). The source declares TCon_nominal = 273.15+30, TAmb_nominal = 273.15+15, QLoa_nominal = 1000. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel heaPum.senTEvaRet.T covers 282.977 to 293.15 K. At 1,728 s, the primary value is 303.15 and the companion is 282.977. Their signed difference is 20.173 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 0 to 1,728 seconds. Subtracting 293.15 from 303.15 gives 10 K. Its location brackets the change within one saved interval of 1,728 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | senTLoaSup.T (K) | heaPum.senTEvaRet.T (K) |
|---|---|---|
0 | 293.15 | 293.15 |
1728 | 303.15 | 282.9769 |
10368 | 303.1503 | 283.142 |
34560 | 298.1603 | 284.0481 |
69120 | 297.1515 | 283.8453 |
103680 | 301.15 | 283.2095 |
138240 | 301.1504 | 283.132 |
172800 | 297.1493 | 283.8453 |
What to check on site
Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.
Cover photograph by Jakub Zerdzicki, via Pexels. The photograph illustrates the subject. Industry Applied produced the figure and calculations from the linked source.