The recorded aquWel.TAquHot[50] temperature spans 12 °C to 15.966 °C in this simulation. That is a change of 3.9655 K. The first saved maximum occurs at 7,776,000 s. The source trace and download retain absolute temperatures in kelvin.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named CoolingOffice. The source file places it under Fluid, Geothermal, Aquifer. We used the 101 stored values for aquWel.TAquHot[50] over the interval 0 to 7,776,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name hea (Heater Cooler u), uPum (Constant), uHea (Constant), aquWel (Multi Well). The source declares QCoo_flow_nominal = 30000, deltaT = 4, cpWat = 4186. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The primary channel spends 84.2% of its saved checkpoints at or above 287.133 source units, halfway between the observed minimum and maximum. Its time-weighted mean under piecewise-linear interpolation is 288.42 source units. These two numbers distinguish how much of the run is spent high from the absolute value of its peak.

Aquifer cooling office. The simulated aquWel.TAquHot[50] channel runs from 285.15 to 289.116 source units over 7,776,000 seconds.
Aquifer cooling office. The simulated aquWel.TAquHot[50] channel runs from 285.15 to 289.116 source units over 7,776,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 933,120 to 1,010,880 seconds. Subtracting 286.315 from 286.569 gives 0.2542 source units. Its location brackets the change within one saved interval of 77,760 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

aquWel.TAquHot[50] (K)

0

285.15

933120

286.3146

1010880

286.5689

1555200

287.972

3110400

288.9965

4665600

289.0958

6220800

289.1118

7776000

289.1155

What to check on site

The thermal history of a borefield matters across repeated loads. Distinguish a fluid outlet reading from pipe wall, grout and far-field temperatures. Record the duration and sign of each heat pulse before comparing an installation with a reference case.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Units in the source model

The component declarations identify the scale of the exported variables. In this run, aquWel.TAquHot[50] uses K. Keep the exact channel name and unit together when exporting data to a historian. Read the component definition.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.