The recorded vol.T temperature spans 16.229 °C to 21.901 °C in this simulation. That is a change of 5.6724 K. The first saved maximum occurs at 29,376 s. The source trace and download retain absolute temperatures in kelvin.
The system being tested
The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named VCLibAirToWater_OneRoomRadiator. The source file places it under Fluid, Heat Pumps, Modular Reversible. We used the 101 stored values for vol.T over the interval 0 to 86,400 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name TAirSouSte (Pulse). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
At 0 s, vol.T is 293.15 K and temRet.T is 323.15 K. Subtracting the second value from the first gives -30 K. This is their largest recorded absolute separation. A difference between an inlet and an outlet, or between a command and a response, need not be a measurement error.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 864 to 1,728 seconds. Subtracting 292.459 from 289.379 gives -3.08 K. Its location brackets the change within one saved interval of 864 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | vol.T (K) | temRet.T (K) |
|---|---|---|
0 | 293.15 | 323.15 |
864 | 292.4589 | 308.8986 |
1728 | 289.3786 | 305.2873 |
17280 | 293.2218 | 311.1066 |
29376 | 295.051 | 310.5493 |
34560 | 293.5405 | 306.343 |
51840 | 293.1338 | 302.2629 |
69120 | 293.3426 | 306.9954 |
86400 | 293.1498 | 306.7523 |
What to check on site
Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.