The published heaPum.modulation signal spans 0 to 47.693 source signal units in the reference run. It starts at 0 and finishes at 26.498. The signed change between those endpoint samples is +26.498 source signal units.

What the reference test measures

The IDEAS model named HeatPump_AirWater comes from the KU Leuven IDEAS project. The saved result covers simulation time 0 to 15,000 seconds. Industry Applied extracted 101 checkpoints for heaPum.modulation and kept the original signed values. The regular output spacing is 150 seconds. The solver may take different internal steps.

The model definition identifies Tset (Constant). These component names let a reader trace the plotted tags to their owning blocks before reproducing the result.

Settings to preserve when repeating the experiment

The published test declares m_flow_nominal = 0.2. Those numbers use the units and component definitions in the linked model. Start with the declared configuration when reproducing the reference result, then vary one setting at a time. Changing the input waveform and the component response in the same comparison makes it difficult to identify the source of a difference.

Reading the two channels

The companion channel heaPum.COP spans 0 to 5.011 ratio across its 101 stored values. The primary trace first reaches its recorded maximum at 13,800 seconds and its minimum at 0 seconds. A time-aligned comparison preserves the meaning and units of each channel.

Air-to-water heat-pump modulation. In the simulated HeatPump_AirWater case, heaPum.modulation ranges from 0 to 47.693 source signal units over 15,000 seconds.
Air-to-water heat-pump modulation. In the simulated HeatPump_AirWater case, heaPum.modulation ranges from 0 to 47.693 source signal units over 15,000 seconds. Figure by Industry Applied.

Reproducing the largest recorded change

Between the stored points at 7,950 and 8,100 seconds, heaPum.modulation changes from 0 to 40.757. Subtracting the earlier reading gives +40.757 source signal units. This interval contains the largest absolute point-to-point change in the saved primary channel. A faster excursion followed by recovery could fit entirely between the two records.

The extrema in the table and figure are extrema of the stored series. A solver’s internal peak, a field logger’s alarm value and a maximum derived from this export can differ. Preserve the sampling settings when comparing results.

Worked data

Simulation time (s)

heaPum.modulation (signal units)

heaPum.COP (ratio)

0

0

0

3750

0

0

7500

0

0

7950

0

0

8100

40.75652

4.454708

11250

0

0

13800

47.69349

4.187778

15000

26.49832

5.010892

Applying the result to an operating site

Compressor modulation is an internal command or operating fraction. It is distinct from heat delivered to the water. Trend power, load temperature and recovered heat before comparing a partial-load operating period with nameplate capacity.

For a local engineering comparison, write the measurement boundary, operating duty and instruments into the test record. Select comparable load or weather periods, then compare the measured trace with the simulated quantities. Establish a local acceptance tolerance using the intended duty and measurement uncertainty.