The thermalZone.CO2Con trace ranges from 400 to 900.077 across 101 saved checkpoints. It begins at 400 and finishes at 449.816 after 604,800 s of test time. The reference export does not state a verified engineering unit for this value. Use its native scale when comparing another run of the same model.
The system being tested
The RWTH Aachen University E.ON Energy Research Center publishes the AixLib test named DemandControlledAHU. The source file places it under Systems, Modular air handler. We used the 101 stored values for thermalZone.CO2Con over the interval 5,961,600 to 6,566,400 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name weaBus1 (Bus). The source declares CO2Con_start = 400, CO2ConAmb = 450. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
At 6,082,560 s, thermalZone.CO2Con reads 899.558 and genericAHU.genericAHUBus.TOdaMea reads 282.051 K. Across the run, the second channel ranges from 277.341 K to 303.15 K. Compare the timing of changes on the two traces. A numerical difference between these channels has no demonstrated physical meaning without matching quantity definitions and units.
Reproduce the calculation
The largest absolute change between consecutive stored points appears from 6,076,512 to 6,082,560 seconds. Subtracting 522.683 from 899.558 gives 376.876 source units. Its location brackets the change within one saved interval of 6,048 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | thermalZone.CO2Con (source units) | genericAHU.genericAHUBus.TOdaMea (K) |
|---|---|---|
5961600 | 400 | 303.15 |
6076512 | 522.6828 | 278.6313 |
6082560 | 899.5585 | 282.0505 |
6203520 | 684.4844 | 285.002 |
6324480 | 454.8531 | 280.3668 |
6433344 | 900.0771 | 283.4854 |
6445440 | 900.0035 | 287.3733 |
6566400 | 449.8162 | 279.445 |
What to check on site
Separate a calculated setpoint from the damper or fan command and from the measured service delivered. Trend the active operating mode, request, actual flow and zone condition on one clock. A sequence can change state correctly while the terminal fails to reach duty.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Units in the source model
The component declarations identify the scale of the exported variables. In this run, genericAHU.genericAHUBus.TOdaMea uses K. Keep the exact channel name and unit together when exporting data to a historian. Read the component definition.