The senTAir_b.T trace covers 20 to 29.665 °C, a temperature span of 9.665 K. The first recorded maximum occurs at 72 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.
The system being tested
Lawrence Berkeley National Laboratory publishes the Buildings test named AirRearDoorHexPassive. The source file places it under Fluid, Data Centers, Racks, Hybrid. We used the 101 stored values for senTAir_b.T over the interval 0 to 7,200 seconds. This is a simulated test with specified inputs and boundaries.
The component declarations name utiAir (Constant), PITAir (Gain), datHal (Boundary p T), senTAir_a (Temperature Two Port). The source declares PAir_nominal = 48*1320, TAirDatHal = 303.15, TReaDooCooIn_nominal = 273.15 + 25, TReaDooCooOut_nominal = 273.15 + 35. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.
Compare the recorded channels
The companion channel rac.PAirFan starts at 0, ends at 2,584 and has a recorded range of 0 to 2,584 source units. Its time span matches the primary channel. Both are included to put the primary response in context. Their numerical scales may represent different physical quantities.

Reproduce the calculation
The largest absolute change between consecutive stored points appears from 0 to 72 seconds. Subtracting 293.15 from 302.815 gives 9.665 K. Its location brackets the change within one saved interval of 72 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.
The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.
Worked data
Simulation time (s) | senTAir_b.T (K) | rac.PAirFan (source units) |
|---|---|---|
0 | 293.15 | 0 |
72 | 302.8153 | 2584.141 |
1440 | 302.8153 | 2584.141 |
2880 | 302.8153 | 2584.141 |
4320 | 302.8153 | 2584.141 |
5760 | 302.8153 | 2584.141 |
7200 | 302.8153 | 2584.141 |
What to check on site
Record the hot and cold boundary conditions as well as the response inside the component. For a steady comparison, check that stored heat has stopped changing. For a transient comparison, keep the timing and the observation location with every reported value.
State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.
Data and source model
Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.