The recorded pla.ctl.ctl.TOut temperature spans 13.3 °C to 19.411 °C in this simulation. That is a change of 6.1113 K. The first saved maximum occurs at 19,662,912 s. The source trace and download retain absolute temperatures in kelvin.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named AirCooled. The source file places it under Templates, Plants, Chillers. We used the 101 stored values for pla.ctl.ctl.TOut over the interval 19,612,800 to 19,699,200 seconds. This is a simulated test with specified inputs and boundaries.

The reference file contains 26 recorded variables. Alongside the primary output there are pla.ctl.ctl.TOut, pla.ctl.dat.TOutChiWatLck, pla.ctl.ctl.staSetCon.capReq.y, pla.cap_nominal, loa.u. The source and the export are linked independently below so that each reading can be traced back to its calculated channel.

Compare the recorded channels

At 19,662,048 s, pla.ctl.ctl.TOut reads 292.27 K and pla.bus.pumChiWatPri.y reads 0.94501. Across the run, the second channel ranges from 0 to 1. Compare the timing of changes on the two traces. A numerical difference between these channels has no demonstrated physical meaning without matching quantity definitions and units.

Air-cooled chiller plant template. The simulated pla.ctl.ctl.TOut channel runs from 286.45 to 292.561 K over 86,400 seconds.
Air-cooled chiller plant template. The simulated pla.ctl.ctl.TOut channel runs from 286.45 to 292.561 K over 86,400 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 19,661,184 to 19,662,048 seconds. Subtracting 291.714 from 292.27 gives 0.5564 K. Its location brackets the change within one saved interval of 864 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

pla.ctl.ctl.TOut (K)

pla.bus.pumChiWatPri.y (source units)

1.96128e+07

287.05

0

1.962749e+07

286.45

0

1.963008e+07

286.45

0

1.964736e+07

289.17

0.4991666

1.966118e+07

291.7141

0.8755651

1.966205e+07

292.2705

0.9450129

1.966291e+07

292.5613

0.9910863

1.966464e+07

291.9756

0.9896398

1.968192e+07

288.0911

0.7635893

1.96992e+07

288.75

0

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.