The recorded TChiWatPriRet.T temperature spans 11.636 °C to 22.849 °C in this simulation. That is a change of 11.213 K. The first saved maximum occurs at 1,040 s. The source trace and download retain absolute temperatures in kelvin.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named ChillerGroupAirCooled. The source file places it under Templates, Plants, Chillers, Components. We used the 101 stored values for TChiWatPriRet.T over the interval 0 to 2,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name outPumChiWatPri (Multiple To Single), pumChiWatPri (Multiple), TChiWatPriSup (Temperature Two Port), mChiWatPri_flow (Mass Flow Rate). The source declares nChi = 3, tau = 10. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

At 1,040 s, TChiWatPriRet.T is 295.999 K and TChiWatPriSup.T is 290.556 K. Subtracting the second value from the first gives 5.4431 K. This is their largest recorded absolute separation. A difference between an inlet and an outlet, or between a command and a response, need not be a measurement error.

Air-cooled chiller group. The simulated TChiWatPriRet.T channel runs from 284.786 to 295.999 K over 2,000 seconds.
Air-cooled chiller group. The simulated TChiWatPriRet.T channel runs from 284.786 to 295.999 K over 2,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 1,000 to 1,020 seconds. Subtracting 293.15 from 295.559 gives 2.409 K. Its location brackets the change within one saved interval of 20 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

TChiWatPriRet.T (K)

TChiWatPriSup.T (K)

0

293.15

293.15

400

293.15

293.15

800

293.15

293.15

1000

293.15

293.15

1020

295.559

292.8027

1040

295.999

290.5559

1200

292.7223

287.5763

1600

285.7735

280.7647

1960

284.7864

280.15

2000

284.7864

280.15

What to check on site

Read the evaporator, condenser and electrical channels at the same duty. The water or air temperatures entering the equipment constrain capacity and efficiency. A compressor command does not specify how much heat actually crosses the useful-load boundary.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.