The senTem_in.T trace covers 20 to 52.6 °C, a temperature span of 32.6 K. The first recorded maximum occurs at 481.25 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named PlugFlowULg. The source file places it under Fluid, Fixed Resistances, Plug Flow Pipes. We used the 101 stored values for senTem_in.T over the interval 0 to 875 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name WaterCityNetwork (Mass Flow Source T), Boiler (Heater T), Sewer1 (Boundary p T), senTem_out (Temperature Two Port). The source declares m_flow_nominal = 1. These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The companion channel senTem_out.T covers 291.35 to 325.489 K. At 113.75 s, the primary value is 325.439 and the companion is 291.762. Their signed difference is 33.677 K, the largest absolute separation on the common grid. Check the two channels’ physical roles before interpreting that difference as any kind of error.

Against data from université de liège. The simulated senTem_in.T channel runs from 293.15 to 325.75 K over 875 seconds.
Against data from université de liège. The simulated senTem_in.T channel runs from 293.15 to 325.75 K over 875 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 0 to 8.75 seconds. Subtracting 293.15 from 310.937 gives 17.787 K. Its location brackets the change within one saved interval of 8.75 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

senTem_in.T (K)

senTem_out.T (K)

0

293.15

291.35

8.75

310.9373

291.3656

175

325.45

301.003

350

325.55

325.1566

481.25

325.75

325.3416

525

325.6864

325.336

700

325.35

325.4793

875

325.35

325.1323

What to check on site

Distinguish the component characteristic from the installed system response. Record the pressure or temperature on both sides as applicable, the direction of flow and the actuator command. Compare a change at constant demand with one caused by a different load.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.