Set the example full-scale range to ±4.096 V. A signed 16-bit result has 32,768 code intervals on its positive half scale. Divide the full-scale magnitude by 32,768, then multiply by the signed reading. With signed adc code at 0, the worked result is 0 on the input voltage (v) scale.
The recorded quantity and the calculated result
Keep three columns in a commissioning export: the original signed adc code, the configuration used in the conversion and the resulting input voltage (v). Recompute the result for the lower, middle and upper worked points before interpreting a field difference. A change in range, units or representation can otherwise be mistaken for a change in the process.
Two points to check independently
Take the neighbouring worked points -8,000 and 0 on the input axis. The results are -1 and 0, giving a signed difference of 1. The table preserves the calculated values before display rounding. These are calculated examples under the stated assumptions. They are not readings from a ProSense installation.

Worked data
Signed ADC code | Input voltage (V) |
|---|---|
-24000 | -3 |
-16000 | -2 |
-8000 | -1 |
0 | 0 |
8000 | 1 |
16000 | 2 |
24000 | 3 |
Checking the ends of the working range
The final interval in this example runs from 0 to 24,000 on the signed adc code axis. Its average change in input voltage (v) per input unit is 0.000125. This is a two-point slope for that interval. To check a spreadsheet or a gateway calculation, enter 24,000 in a separate test row and compare its result against 3 at the displayed precision.
Installation and interpretation
A negative differential reading is a valid mathematical result. It does not extend the permitted absolute voltage range at either input pin. Preserve the selected input pair and gain setting in the exported record.
For a repeatable verification, capture a small known case and a second case well away from it. Check whether the difference follows the response in the table, then restore the working configuration and repeat one reading. Store a separate status field for missing or invalid input. Substituting zero would make a dropped observation indistinguishable from a legitimate numerical zero.
Implementation and worked data
The source implementation is maintained in the .NET IoT device project. The component notes and manufacturer references document the supported device and its interfaces. Download the worked numerical example.