The zonHVAC.TAir trace covers 6.033 to 39.047 °C, a temperature span of 33.014 K. The first recorded maximum occurs at 9,123,840 seconds. The numerical source and data table retain the original kelvin values. Subtract 273.15 only when converting an absolute temperature to Celsius.

The system being tested

Lawrence Berkeley National Laboratory publishes the Buildings test named FreeFloatingHVAC. The source file places it under Thermal Zones, ISO13790. We used the 101 stored values for zonHVAC.TAir over the interval 8,640,000 to 9,504,000 seconds. This is a simulated test with specified inputs and boundaries.

The component declarations name weaDat (Reader TMY3), zonHVAC (Zone HVAC), intGains (Constant), latGains (Constant). These identifiers can be found in the linked model definition. Check how they connect to the plotted quantity before comparing it with a field meter or a differently named controller tag.

Compare the recorded channels

The primary channel spends 44.6% of its saved checkpoints at or above 295.69 K, halfway between the observed minimum and maximum. Its time-weighted mean under piecewise-linear interpolation is 294.808 K. These two numbers distinguish how much of the run is spent high from the absolute value of its peak.

5 r1 c HVAC thermal zone in free-floating conditions. The simulated zonHVAC.TAir channel runs from 279.183 to 312.197 K over 864,000 seconds.
5 r1 c HVAC thermal zone in free-floating conditions. The simulated zonHVAC.TAir channel runs from 279.183 to 312.197 K over 864,000 seconds. Figure by Industry Applied.

Reproduce the calculation

The largest absolute change between consecutive stored points appears from 8,925,120 to 8,933,760 seconds. Subtracting 282.619 from 291.178 gives 8.56 K. Its location brackets the change within one saved interval of 8,640 seconds. It does not identify an unobserved instantaneous peak or the exact crossing time.

The worked table retains the first and last points, the primary maximum and minimum, the largest adjacent change and a spread of checkpoints across the run. Rounding is for presentation. Use the full linked reference series to repeat integrals or compare events between checkpoints. The archived sampling interval need not match the simulation solver’s internal step.

Worked data

Simulation time (s)

zonHVAC.TAir (K)

8640000

293.15

8812800

282.0417

8925120

282.6186

8933760

291.1783

8985600

294.9253

9123840

312.197

9158400

299.2508

9331200

299.2935

9504000

279.1832

What to check on site

Keep the occupied schedule, weather boundary and zone definition with the result. A change in a simulated room condition can reflect the boundary assumptions as well as the component under study. Compare occupied periods and maintain the same observation location.

State the operating duty, measurement location and expected tolerance before evaluating a local trend. Re-run the comparison with the installed controls and instruments during a representative operating period. Retain the native units and the raw export so that a later change in software or presentation can be investigated.

Data and source model

Published model and component definitions. Numerical reference series. Simulation and plot commands. Download the worked checkpoints in CSV format.