Why a pump vibration trend can show the wrong frequency
A slow sampler can turn a real vibration component into a lower apparent frequency. Check the analogue bandwidth before comparing two monitoring systems.

A pump historian shows a steady feature near 20 Hz. A portable analyser on the same housing sees a strong component at 80 Hz. The discrepancy may come from the measurement chain. A transmitter reporting one overall value each minute and a device sampling an actual waveform also produce fundamentally different records.
Distinguish the waveform from its reporting interval
Find the waveform sampling rate, the analogue filter and the frequency range used to calculate a reported value. A reporting interval controls when summaries arrive. It cannot recover detail removed upstream. Record the sensor position, mounting, axis and machine operating state so that a repeated comparison has meaning.
In an ideal sampling example, an 80 Hz sine sampled at 100 samples per second appears at 20 Hz in the sampled baseband. The 50 Hz Nyquist frequency is below the original component. A suitable analogue anti-alias filter and a sampling rate suited to the band of interest prevent that interpretation error.

What to check on site
Ask whether the historian channel stores waveforms, spectra or overall levels.
Record filter settings and observe the same machine duty during a comparison.
Repeat with a suitable acquisition bandwidth before assigning a mechanical fault.
A water utility can use this check when comparing a remote pump alert with a portable survey. A single line in a spectrum is a reason to investigate the chain and the machine, not enough evidence to replace a bearing.
Sources and photograph
A pump historian shows a steady feature near 20 Hz. A portable analyser on the same housing sees a strong component at 80 Hz. The discrepancy may come from the measurement chain. A transmitter reporting one overall value each minute and a device sampling an actual waveform also produce fundamentally different records.
Distinguish the waveform from its reporting interval
Find the waveform sampling rate, the analogue filter and the frequency range used to calculate a reported value. A reporting interval controls when summaries arrive. It cannot recover detail removed upstream. Record the sensor position, mounting, axis and machine operating state so that a repeated comparison has meaning.
In an ideal sampling example, an 80 Hz sine sampled at 100 samples per second appears at 20 Hz in the sampled baseband. The 50 Hz Nyquist frequency is below the original component. A suitable analogue anti-alias filter and a sampling rate suited to the band of interest prevent that interpretation error.

What to check on site
Ask whether the historian channel stores waveforms, spectra or overall levels.
Record filter settings and observe the same machine duty during a comparison.
Repeat with a suitable acquisition bandwidth before assigning a mechanical fault.
A water utility can use this check when comparing a remote pump alert with a portable survey. A single line in a spectrum is a reason to investigate the chain and the machine, not enough evidence to replace a bearing.