The OPC UA server sampled a short event. Why did the historian miss it?
Compare sampling, queue capacity and publishing time. A real transition can be sampled and still be replaced before delivery.
An OPC UA monitored item can sample changes faster than its subscription publishes notifications. If the monitored item keeps only the latest change, a transition can enter the queue and then be replaced before the client receives it. Faster sampling alone cannot preserve every short event.
Follow one second of activity
Take a simplified example with an observed initial low value. Between two publishes, the sampled state changes high at 0.2 s, low at 0.4 s, high at 0.6 s and low at 0.8 s. With a one-value queue, the last low can be the only value available at the next publish. A queue holding the most recent two changes could deliver high and low. With room for all four under the assumed settings, all four can be retained.

Worked data
Available queue slots | Changes generated | Changes retained |
1 | 4 | 1 |
2 | 4 | 2 |
4 | 4 | 4 |
Download the figures in this worked example (CSV)
Inspect the settings the server actually revised
Read the monitored item’s revised sampling interval and queue size, the discard policy, applicable data-change filter and the subscription’s publishing interval. An application’s requested values may differ from the values a server supports. Examine overflow indications where the configuration exposes them, then check whether the downstream historian applies another filter or aggregation step.
This is a history-preservation question, not proof of the physical event’s duration. A pulse entirely between samples can be missed before queueing is relevant. An application that must count every transition may need an appropriate event or counter at the source. Use an approved replay or offline test signal to distinguish acquisition, queueing, delivery and historian storage without affecting a production process.
Sources
OPC Foundation · Monitoring parameters and queue size
Cover illustration by Industry Applied, generated with AI. Monitoring equipment beside a factory conveyor.
Related reading
An OPC UA monitored item can sample changes faster than its subscription publishes notifications. If the monitored item keeps only the latest change, a transition can enter the queue and then be replaced before the client receives it. Faster sampling alone cannot preserve every short event.
Follow one second of activity
Take a simplified example with an observed initial low value. Between two publishes, the sampled state changes high at 0.2 s, low at 0.4 s, high at 0.6 s and low at 0.8 s. With a one-value queue, the last low can be the only value available at the next publish. A queue holding the most recent two changes could deliver high and low. With room for all four under the assumed settings, all four can be retained.

Worked data
Available queue slots | Changes generated | Changes retained |
1 | 4 | 1 |
2 | 4 | 2 |
4 | 4 | 4 |
Download the figures in this worked example (CSV)
Inspect the settings the server actually revised
Read the monitored item’s revised sampling interval and queue size, the discard policy, applicable data-change filter and the subscription’s publishing interval. An application’s requested values may differ from the values a server supports. Examine overflow indications where the configuration exposes them, then check whether the downstream historian applies another filter or aggregation step.
This is a history-preservation question, not proof of the physical event’s duration. A pulse entirely between samples can be missed before queueing is relevant. An application that must count every transition may need an appropriate event or counter at the source. Use an approved replay or offline test signal to distinguish acquisition, queueing, delivery and historian storage without affecting a production process.